Close

Raise your Query

Hi! Simply click below and type your query.

Our experts will reply you very soon.

WhatsApp Us

Testing House




TD325P VITD 12/1250-25P


Business Type Manufacturer, Exporter, Supplier, Retailer, Wholesaler

Preferred Buyer From

Location Anywhere in India

Cost-efficient, require low power consumption, safe design and easy to operate are some of the features that describe Vacuum Interrupter For Circuit Breaker. The Vacuum Interrupter For Circuit Breakers, which we provide, are not affected by pollution, since the Vacuum Interrupter is hermetically sealed. Moreover, the Vacuum Interrupter For Circuit Breaker is preferred for its high shelf-life.

Electrical Ratings (3Phase) Symmetrical Basis
Rated Frequency 50/60Hz
Rated Maximum Line to Line Voltage 12kV,r.m.s
Rated Power Frequency Withstand Voltage : Air 42kV,r.m.s
Rated Impulse Withstand Voltage : Air 95kV,Peak
Rated Normal Current 1250A
Rated Short- Circuit Current ( 3 Phase Symmetrical Basis) 25kA,r.m.s
Percentage D.C. Component of Rated S.C. Breaking Current 50.00%
Rated Short-Circuit Making Current 63kA,Peak
Rated Duration of Short Time Current 4s
Rated Short-Time Withstand Current 25kA,r.m.s
Rated Peak Withstand Current 63kA,r.m.s
*Maximum Contact Resistance at Minimum Closing Force 19Micro ohms
*Rated Breaking Current of Single Capacitor Bank 630A,r.m.s
*Rated Breaking Current of Back-to-Back Capacitor Bank 400A,r.m.s
Rated operating sequence o-0.3s-co-180s-co
Mechanical Data
Interrupter Weight (Approx.) 2.39kg
Moving Part Weight (Approx.) 0.82kg
Closing Force due to Bellow and Atmospheric 80±40N
Force Required to Hold Contacts open at Full Stroke 120±50N
Mechanical Requirements (Ref. Vcb)
Contact Stroke 8±1 mm
Opening Speed (average of 75 contact gap) 1.1±0.2m/Sec
Maximum Overtravel During Opening 2mm
Maximun Rebound During Opening 2mm
Closing Speed (average of last 30% contact gap) 0.6±0.2m/Sec
Maximum Contact Bounse Duration (with maximum 2 bounces) â‰Â¤2ms
Rated Contact Compressive Force 2000±200N
Closing and Opening non-simultaneity of three-phase Contacts â‰Â¤2ms
Life (Estimated)
Electrical Life at Rated Normal Current 50,000 Operations
Electrical Life at Rated Short Circuit Current 100 Operations
Mechanical Life 50,000 Operations
Contact Erosion Limit 3mm
Shelf Life 20Years

Note
  • Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-200 and JB 8738-2008.
  • * Rated Characteristics to be given on request.
Read More...


Looking for "TD325P VITD 12/1250-25P" ?

Explore More Products